PSM-660U Ultrasonic Pump Station Flow Monitor Controller

Specifications

Electronics  
Power Requirements:

120/220 VAC, ±15%,50/60 Hz, 12-24 VDC @ 15W max.

Temperature: 25°F to 125°F (-5°F with opt. heater)
Display: 2 line x 20 character, Alphanumeric, LCD with LED Backlighting
Totalizer (counter)

One, 8 digit accumulative with programmable multiplier of x1, x10, x100, x1000.

200 daily, 8 digit totalizers, Data Logging

Outputs:

Two (2) 4-20 mA isolated into 1000 ohm max.; RS-232 (USB port, MODEM opt.); 5 relay outputs - SPDT 5A/250 VAC
Flow Range: 0-999,999 GPM
Span Range: 0-24.00" to 0-250.00" full scale
Dead Band (blanking): 12" to 36" adjustable
Resolution: 0.1 GAL/MIN flow; 0.01" level
Accuracy*: ±1.0% of Range or better. ±1.0 second run time, Calculated error less than ±0.1%
Memory: Flash and non-volatile RAM
Equations: Circular, Rectangular, Square wet wells
Data Log:

200 Day, 24 hour Summary

Time stamped detailed pump cycle summary

Time stamped EVENT list to record monitor actions

Download:

Directly to serial printer (24 hour summary only) or all data to PC COM port or through MODEM.

All Data is preformatted.

 

 

* field conditions, such as turbulance, foam etc., may affect the apparent accuracy.

 

 

Sensor  
Exposed Material: PVC, epoxy (Teflon opt.)
Beam Pattern: 5° Conical (2.5° from centerline)
Temperature: -40°F to 160°F exposure
Cable: 30 foot corrosion resistant, 1000 ft. max., twisted pair shielded, Belden#8451, Max 60 Volts Pulsed applied
Dimensions: 3.0" dia. x 4.2" len.
Mounting: 3/4" NPT male
Temp Probe: Built into Sensor Head, ±3°F
Enclosure  
Material: Fiberglass with clear hinged Polycarbonate cover
Rating: NEMA 4X, IP65, Water-Tight, Dust-Tight and Corrosion-Resistant - CSA, UL listed
Dimensions: 7.2" x 11.8" x 6.8"
Mounting: 4.92" x 12.3" with stainless steel mounting feet

Options

Heater/Thermostat, PVC Sensor Mounting Bracket, Sensor Cable, USB Port, MODEM ....

Warranty