| Electronics |
|
| Power
Requirements: |
120/220 VAC,
±15%,50/60 Hz, 12-24 VDC @ 15W max.
|
| Temperature: |
25°F
to 125°F (-5°F with opt. heater) |
| Display: |
2
line x 20 character, Alphanumeric, LCD with LED Backlighting |
|
|
Two 4-20 mA
isolated into 1000 ohm each. RS-232 output, 5
programmable alarm relay outputs with separate ON/OFF settings,
SPDT 5A/250 VAC
|
| Span
Range: |
0-1.00"
to 0-200.00" full scale |
| Dead
Band (blanking): |
12" to 36" adjustable |
| Resolution: |
0.01
inch |
| Accuracy*: |
±0.8%
of Range or better. Calculated error less than ±0.04% |
| Memory: |
Flash
and non-volatile RAM |
| Tank
Equations: |
Cylindrical,
Horizontal, Spherical, Rectangular, Square |
| Data
Log: |
200
Day Summary: min, max, avg level, Total Gallons. Time Stamped avg
LEVEL with programmable log rate of 00-99 minutes in 1 minute icrements |
| Download: |
Directly
to serial printer or PC/Laptop. Initiate from PC or from Level Monitor.
Data is preformatted. |
|
|
*
field conditions, such as turbulance, foam etc., may affect the apparent
accuracy or performance |
|
| Sensor
|
|
| Exposed
Material: |
PVC
- (Teflon Optional) |
| Beam
Pattern: |
5°
Conical (2.5° from centerline) |
| Temperature: |
-40°F
to 160°F |
| Cable: |
30
foot corrosion resistant, 1000 ft. max., twisted pair shielded, Belden#8451,
Max 60 Volts Pulsed applied |
| Dimensions: |
2.95"
dia. x 4.2" len. |
| Mounting: |
3/4"
NPT male |
| Temp
Probe: |
Built
into Sensor Head |
| Enclosure |
|
| Material: |
Fiberglass
with clear hinged Polycarbonate cover |
| Rating: |
NEMA
4X, IP65, Water-Tight, Dust-Tight and Corrosion-Resistant - CSA, UL
listed |
| Dimensions: |
7.2"
x 11.8" x 6.8" |
| Mounting: |
4.92"
x 12.3" with stainless steel mounting feet |
Options
Heater/Thermostat,
PVC Sensor Mounting Bracket, USB Port, Sensor Cable ...
Warranty
Systems are pre-tested
and quality control inspected before shipping. Warranty is against defects
in parts and workmanship for a period of one (1) year.
Specifications and design subject to change without notice.
Note:
ERS-560DX does not have Relay Outputs, Data Logging and RS-232 output.
|
|
CONTROL
ELECTRONICS, INC. P.O. Box 330, Brandamore, PA 19316
(610)
942-3190 FAX: (610) 942-3672
RETURN